■2. GOT installation status check sheet
Check the actual installation status of the GOT used according to the GOT installation status described in the upper
rows of items (1) to (7).
When the corrective actions described in the lower rows need to be taken, take the actions.
Only when the corrective actions are taken, put a check mark in the check box of "Effective" or "Ineffective" depending
on the results of the actions.
(1) Wiring inside
Actual status
Corrective action
for when the
cables are
crossed each
other
(2) Outside the panel
Actual
status
Figur
e
A
Corrective
action for
when they
Figur
are bundled
e
B
NFB
MC
MC
RA
RA
NFB
MC
MC
RA
RA
Power line
Communication cable
Power line
Communication cable
Wiring
Separator
Power
duct
line
100mm or more
Signal
Power
line
line
Power lines such as power supply
cables or servo amplifier drive cables
and communication cables are
crossed each other in the wiring duct
in the control panel.
Wiring the power lines and the
communication cables to keep them
away from each other in the control
panel will help minimize noise
interference.
Power lines and communication
cables are bundled together.
Setting outlets of the power lines
and the communication cables
separately, as shown in Figure A,
will help minimize noise
interference. In the duct, keeping
the communication cables away
from the power lines or using a
metal separator, as shown in Figure
Communication
B, can reduce noise interference.
cable
22.1 GOT Restoration Sheets
Crossed
Not crossed
22
Effective
Ineffective
Bundled
Not bundled
Effective
Ineffective
22 - 5

Hide quick links: