■3. Restoration
Error
Setting data (files and data)
cannot be written into the
controller.
The restoration cannot be
executed because passwords for
files of the controller are set.
15 - 62
15.9 Errors and Corrective Actions
Cause
The GOT cannot communicate with the
controller.
The target controller of the restoration is a
different kind of controller from the target
controller of the backup.
• The passwords for files written in the
controller are changed.
Corrective action
Check the following.
GOT
• Check if the cable is correctly connected to the GOT.
• Check if the correct communication driver is installed
on the GOT.
• Check if the communication settings are correctly set.
Controller
• Check if the parameters are set.
• Check if the cable is correctly connected to the
controller.
• Check if the controller is turned on.
• Check if the system configuration for the restoration is
the same as that for the backup.
• Check if the target controller of the restoration is the
same as that of the backup or the same kind of
controller.
Check with the administrator of the system regarding the
passwords for files of the controller.