■4. Non-Mitsubishi PLC, inverter, and servo amplifier connections
Create the cables (RS-232 cable, RS-422/485 cable) for connecting the GOT and a controller by yourself.
For how to create a cable, refer to the following.
GOT side
100 or less
(3.94)
5 - 6
5.2 EMC Directive Requirements
GOT2000 Series Connection Manual For GT Works3 Version1
POINT
POINT
POINT
Treatment of the RS-232 cable and RS-422/485 cable
When the GOT is connected to a controller, configure the system according to the EMC Directive
specifications for the controller.
The following shows the recommended instructions to comply with the EMC Directive.
However, the manufacturer of the equipment must determine the method to comply with the EMC
Directive and conformance to the directive.
(1) RS-422/485 cable
• When connecting each signal wire (except SG and FG wires), twist two signal wires as
shown below.
SDA
SDB
RDA
RDB
• Connect two or more SG wires.
(2) RS-232 cable
• Twist each signal wire (except SG and FG wires) with the SG wire.
RD
SD
DTR
DSR
SG
• Install a ferrite core to the cable in the positions as shown in the figure below.
• Strip off the sheath at the both ends of the cable as shown in the figure below to expose
braided shield for grounding.
The braided shield sections are used for grounding with a cable clamp.
Ferrite core
(ZCAT3035-1330)
230 or less
40
(9.06)
(1.58)
40
230 or less
(1.58)
(9.06)
RDA
RDB
SDA
SDB
SD
RD
DSR
DTR
SG
PLC CPU side
100 or less
Unit: mm (inch)
(3.94)