5. EMC DIRECTIVE
5.1
Overview
For the products sold in European countries, the conformance to the EMC Directive, which is one of the European
Directives, has been a legal obligation since 1996.
Manufacturers, who recognize that their products comply with the EMC Directive must declare that their products comply
with the Directives and put a CE mark on the products.
■1. Sales representative in Europe
The sales representative in Europe is as shown below.
Company name: Mitsubishi Electric Europe BV
Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany
5.1.1
Conforming standards in the EMC Directive
The GOT complies with the following standards in the EMC Directive.
Applied
Test standard
standard
CISPR16-2-3
Radiated noise
IEC61000-4-2
Electrostatic immunity
IEC61000-4-3
Radiated electromagnetic
field, amplitude modulation
IEC61000-4-4
Fast transient burst noise
EN61131-2
: 2007
IEC61000-4-5
Surge immunity
IEC61000-4-6
Conducted RF immunity
IEC61000-4-8
Power supply frequency
magnetic field immunity
*1
The GOT is an open type device (designed to be integrated in equipment).
Make sure to install the GOT on a control panel.
This test item is conducted in the condition where the GOT is installed on a control panel and combined with the MITSUBISHI
PLC.
*2
QP: Quasi-peak value, Mean: Average value
*3
This test item is conducted in the following conditions.
• 30 MHz to 230 MHz
QP: 40 dBμV/m (measured at 10 m)
• 230MHz to 1000MHz
QP: 47 dBμV/m (measured at 10 m)
Test details
Test for measuring electromagnetic
*1
emissions from the product
Immunity test in which static electricity
is applied to the cabinet of the
*1
equipment
Immunity test in which an electric field
is applied to the product
*1
Immunity test in which burst noise is
applied to the power cables and the
*1
signal lines
Immunity test in which lightening surge
*1
is applied to the product
Immunity test in which a noise
inducted on the power cable and the
*1
signal lines is applied
Test for checking normal operations
under the circumstance exposed to the
ferromagnetic field noise of the power
supply frequency (50/60 Hz)
Standard value
• 30 MHz to 230 MHz
QP: 30 dBμV/m (measured at 30 m)
• 230 MHz to 1000 MHz
QP: 37 dBμV/m (measured at 30 m)
• Contact discharge: ±4 kV
• Aerial discharge: ±8 kV
80 MHz to 1000 MHz: 10 V/m
1.4 GHz to 2 GHz: 3 V/m
2.0 GHz to 2.7 GHz: 1 V/m
(80% amplitude modulation at 1 kHz)
Power cable: 1 kV
Digital I/O: 1 kV
Analog I/O: 1 kV
Signal cable: 1 kV
• AC power type
Power cable (between cable and ground): ±2
kV
Power cable (between cables): ±1 kV
Data communication port: ±1 kV
• DC power type
Power cable (between cable and ground):
±0.5 kV
Power cable (between cables): ±0.5 kV
Data communication port: ±1 kV
Power cable: 10 V
Data communication port: 10 V
30 A/m
5.1 Overview
5
*2*3
*2*3
5 - 1