Using The Rec Ipe Trans Fer Ob Ject - Maple Systems Silver Series Installation And Operation Manual

Operator interface terminal
Hide thumbs Also See for Silver Series:
Table of Contents

Advertisement

240
2. Click the Add... button. The Data Transfer Object dialog box appears.
3. Use the Description: box to enter a title for the Data Transfer part. A description is not
necessary but does help you identify the purpose of the part.
4. In the Source address frame, select the PLC coils or registers that are to be copied. If the
Address mode is Word, then the No. of words box is used to specify the total number of
16-bit registers to copy. The range is 1 to 16.
5. In the Destination address frame, select the PLC coils or registers that receive the data.
6. In the Attribute frame, for the Address mode: setting click Word or Bit. Use the Word
setting for data transfer of 16-bit registers. Use the Bit for data transfer of coils. If Bit is
selected, enter the total number of bits that are to be transferred in the Number of bits: box.
The range is 1 to 255.
7. The Interval: setting in the Attribute frame, is used to select the period at which the data is
transferred. Select 0 for continuous data transfer. Range is 0 to 25.5 seconds in 0.1 second
increments. Note that selecting a smaller period will decrease the amount of OIT processing
time that can be allocated to other tasks.
8. Click OK to close the Data Transfer Object's Attributes dialog box. The Data Transfer
Object dialog box reappears with the new entry listed. You can edit the attributes of an
existing Data Transfer object by clicking on the Setting... button. Any entries can be deleted
by clicking on the Delete button.
9. Click Close to close the Data Transfer Object dialog box. The Data Transfer Object is active
no matter what windows are currently displayed on the OIT screen. Therefore, you do not
have to place the object onto a window screen.

Using the Rec ipe Trans fer Ob ject

The Recipe Transfer Object is used to download or save data from one or more PLC registers to the OIT's internal
registers that are reserved for recipes. This occurs when the object is activated by a press from the OIT operator.
Each Object created can transfer from 1-32767 continuous registers.
Recipes are not available in the HMI504T.
1010-1001a, Rev 02