Maple Systems HMI5000 Series Quick Start Manual

Human/machine interface terminals communication with allen bradley plc5e-series controllers

Advertisement

Quick Links

C O N T R O L L E R
Maple Model(s)
HMI5000 Series
Summary
Maple Systems' HMI5000 Series Human/Machine Interface Terminals (Maple HMIs)
communicate with Allen Bradley PLC5e-series controllers using the DF1/PCCC protocol,
using the DF1 Typed Read and Typed Write commands. When configured with EZware-5000,
the Maple HMI is the master in a single master, multiple slave format. Please refer to the
HMI5000 Series Programming Manual for information on connecting multiple Maple HMIs to
a single PLC.
Compatible PLCs
PLC Family
PLC-5

Communications Cable

The Maple HMI should be connected to the ethernet port on the PLC or
communications cables offered by Maple Systems as well as cable assembly instructions to
assist you in assembling your own communications cable are available on our website at
www.maplesystems.com.
WARNING If your communications cable is not wired exactly as shown in our cable
assembly instructions, damage to the HMI or loss of communications can
result.
Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333 – www.maplesystems.com
.
1036-0175
I N F O R M A T I O N
PLC or Controller
Allen-Bradley
PLC-5/xxE Series
(Ethernet)
PLC Model
PLC-5/20E, PLC-5/40E, PLC-5/80E;
1785-ENET/C Module
Page 1 of 6
S H E E T
module.
A list of
Rev. 01, 03/04/2011

Advertisement

loading

Summary of Contents for Maple Systems HMI5000 Series

  • Page 1: Communications Cable

    WARNING If your communications cable is not wired exactly as shown in our cable assembly instructions, damage to the HMI or loss of communications can result. Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333 – www.maplesystems.com 1036-0175 Page 1 of 6...
  • Page 2 Accessible PLC Memory Register Memory The following table lists the PLC’s register memory ranges that the Maple HMIs are able to access. Please note that your PLC’s memory range may be smaller or larger than that supported by these HMIs. The following register memory can be displayed in 16 or 32-bit format on the Maple HMI.
  • Page 3 Do not configure the HMI to write to any PLC memory address which should only be written to by the PLC. Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333 – www.maplesystems.com 1036-0175 Page 3 of 6...
  • Page 4 EZware Settings The following table lists the communications settings that must be configured in EZware. These settings can be found in the Edit-System Parameters menu under the Device tab. Please note:  The Recommended Settings column provides the recommended setting based upon the default settings most commonly used in the Allen- Bradley PLC-5e Series controller.
  • Page 5: Communication Errors

    Note: in the event that the PLC does not respond, the PLC No Response window will be displayed, but the value in LW8999 will still be 0. Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333 – www.maplesystems.com 1036-0175 Page 5 of 6 Rev.
  • Page 6 Communication Errors are almost always caused by some type of mismatch between the address specified in the HMI and the Data Table in the PLC. Common problems are:  An object in the HMI is configured to read N7:250, but the N7 data file in the PLC is configured only up to N7:200.