Page 1
HMI5000B Series Installation Guide Introduction Thank you for purchasing a Maple Systems HMI5000B Series graphic industrial operator interface terminal. This booklet describes the steps necessary for installing the following models: HMI5040B HMI5070B HMI5100BN HMI5040BN HMI5070BN The HMI5000B Series touchscreens are configured using the EZwarePlus software (purchased separately).
Page 2
HMI5000B Series Touchscreen Power Connector Mounting Clamp Kit HMI5000B Series Installation Guide Warranty A copy of the Warranty and Limitation of Liability is contained in the product box. It can also be found on the Maple Systems website. 1010-1051 Rev 00 www.maplesystems.com...
Page 3
Web: www.maplesystems.com Installation of HMIs Information furnished by Maple Systems is believed to be accurate and reliable. However, no responsibility is assumed by Maple Systems for the use of this information, or for any infringements of patents or other rights of third parties which may result from its use.
Page 4
HMI5000B Installation Guide Environmental Considerations The HMI is designed to operate in temperatures from 0° to 50°C (32° to 122°F). It is intended for indoor installations and may not be suitable for use in certain outdoor applications. Avoid installing the HMI in environments with severe mechanical vibration or shocks.
HMI5000B Installation Guide Control Panel Design Guidelines Pay careful attention to the placement of system components and associated cable routing. This can significantly enhance the performance and integrity of the control application. Cable Routing and Noise Immunity Follow these guidelines when routing cables to the HMI: ...
For a more in-depth overview of ground wiring techniques, refer to Technical Note #1027, “Ground Wiring and Electrical Noise Reduction” in the Technical Notes section of the Maple Systems website. Installation It is necessary to follow all installation procedures described in this chapter for electrical noise immunity and CE compliance.
Page 8
HMI. The power cable for the HMI should be 18AWG, 2-conductor wire with a shield drain wire and protective shield (foil/braid). Cable (P/N 6030-0009) may be purchased by the foot from Maple Systems for constructing power cables. Always run the DC ground wire directly back to the signal return of the power supply.
Page 9
Cutout dimensions for each particular HMI model are available for print and download from the Support Center-Dimensional Drawings section of the Maple Systems website. The area of the panel or mounting surface where the gasket comes into contact must be flat and free of scratches, pits, and other features that prevent the gasket from sealing properly.
P/N 7431-0119 Ethernet Micro USB (Crossover) HMI5040B, HMI5070B HMI5040BN, HMI5070BN, HMI5100BN Ethernet If using a switch or router between the PC and the HMI, use a straight- through or crossover cable as required by the switch or router. In order to download a project to the HMI over Ethernet, the HMI must be assigned a unique IP address that is on the same subnet as the development PC.
If there is a difference in ground potential (voltage), making a connection via a USB cable can complete a ground loop that may damage the HMI and PC. The Maple Systems Micro USB Configuration Cable (P/N 7431-0119) is recommended for connecting the HMI to the PC.
Page 13
HMI5000B Installation Guide DE9P DE9S COM2 COM2 COM3 COM1 COM3 Pin# Pin# [RS-485 2 wire] [RS-485 4 wire] [RS-485 2 wire] [RS-232] [RS-232] Data- Data+ Data- Data+ HMI5100BN Note: COM2 [RS-485 2W] and COM3 [RS-485 2W] support the Siemens MPI 187.5K multi-point interface. However, only one COM port can be used with the Siemens MPI interface at a time.
Need help?
Do you have a question about the HMI5040BN and is the answer not in the manual?
Questions and answers