Maple Systems Silver Series Installation And Operation Manual page 169

Operator interface terminal
Hide thumbs Also See for Silver Series:
Table of Contents

Advertisement

Rep re senting Data with Graph ics Ob jects
PLC Control Object; Change
9052
Window option – disable clearing
PLC register
9053,9054
Reserved for future use
Loss of communications to PLC;
9055
Writing to PLC register control
Loss of communications to PLC;
9056
Touchscreen control
9057-9059
Reserved for future use
Keypad Control; AI or NI located
9060
on left side of keypad window
Keypad Control; AI or NI located
9061
on left side of keypad window
Keypad Control; AI or NI located
9062
on left top side of keypad window
Keypad Control; AI or NI located
9063
on left bottom side of keypad
window
Keypad Control; AI or NI located
9064
on right side of keypad window
Keypad Control; AI or NI located
9065
on right side of keypad window
Keypad Control; AI or NI located
9066
on right top side of keypad
window
Keypad Control; AI or NI located
9067
on right bottom side of keypad
window
Keypad Control; AI or NI located
9068
on any side of keypad window
Keypad Control; AI or NI located
9069
on any side of keypad window
9070-9079
Reserved for future use
Keypad control; AI or NI located
9080
on TOP side of keypad window.
Keypad Control: AI or NI located
9081
on BOTTOM side of keypad
window.
9082-9089
Reserved for future use
9090
Clear Data Event Log
9091
Contrast Up
9092
Contrast Down
9093-9099
Reserved for future use
Set this bit to prevent the OIT from clearing the PLC register used
R/W
for the Change Window option
If OIT loses connection to the PLC while it is trying to write to a
PLC register, set this bit to continue to send Write command after
communications is reestablished. Clearing this bit prevents the
OIT from issuing the Write command after connection is
R/W
reestablished.
0: Any write to PLC command will be killed.
1: Any write to PLC command will be continuously retired.
If OIT loses connection to the PLC, setting this bit disables the
R/W
touchscreen until communications is reestablished.
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the left side of the keypad. The
RdOnly
OIT clears this bit when user presses the Enter or ESC keys.
Note: this bit can be used to control Keypad popup.
RdOnly
Same as LB9060
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the left side of the keypad on the
RdOnly
top half. The OIT clears this bit when user presses the Enter or
ESC keys.
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the left side of the keypad on the
RdOnly
bottom half. The OIT clears this bit when user presses the Enter
or ESC keys.
The OIT sets this bit when user edits a Numeric Input Object or
RdOnly
ASCII Input Object located on the right side of the keypad. The
OIT clears this bit when user presses the Enter or ESC keys.
RdOnly
Same as LB9064
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the right side of the keypad on the
RdOnly
top half. The OIT clears this bit when user presses the Enter or
ESC keys.
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the right side of the keypad on the
RdOnly
bottom half. The OIT clears this bit when user presses the Enter
or ESC keys.
The OIT sets this bit when user edits a Numeric Input Object or
RdOnly
ASCII Input Object located on any side of the keypad. The OIT
clears this bit when user presses the Enter or ESC keys.
RdOnly
Same as LB9068
The OIT sets this bit when user edits a Numeric Input Object or
RdOnly
ASCII Input Object located on the TOP side of the touchscreen.
The OIT clears this bit when user presses the Enter or ESC keys.
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the BOTTOM side of the
RdOnly
touchscreen. The OIT clears this bit when user presses the Enter
or ESC keys.
2.6.0 -- This bit is used to clear the event data. Set to clear data.
R/W
After it is set, the OIT automatically clears the bit after data is
erased.
Write
V 2.6.0 -- Use to increment the contrast.
Write
V. 2.6.0 -- Use to decrement the contrast.
165
1010-1001a, Rev 02