Section 2 Relay Engineering Process - ABB Relion Series Engineering Manual

Grid automation
Hide thumbs Also See for Relion Series:
Table of Contents

Advertisement

1MRS757810 C
Section 2
REC615 and RER615
Engineering Manual
Relay engineering process
PCM600 is used for various tasks in the protection relay engineering process.
Relay engineering management
Organizing the bay protection relays in the structure of the substation by
defining voltage levels and bays below the substation. PCM600 manages
the project.
Configuring the protection relay functions (for example, protection and
control functions) by using the Application Configuration tool.
Configuring the parameters and setting values for the protection relay itself
and for the process functions by using the Parameter Setting tool.
Drawing single-line diagrams and making links to dynamic process values
by using Graphical Display Editor. The single-line diagrams are displayed
in LHMI and WHMI on the bay protection relay.
Configuring connections between the application configuration function
blocks and physical hardware inputs and outputs by using the Signal Matrix
tool or the Application Configuration tool.
Configuring the events shown on the LHMI using the HMI Event Filtering
tool.
Reusing configurations from older protection relay versions using the
Configuration Migration tool.
Communication management
IEC 61850 station communication engineering is done using the internal
IEC 61850 Configuration tool or the separate IET600. PCM600 interacts
with IET600 by importing and exporting SCL files.
Configuring the GOOSE receiving data connections to the protection
relay's application configuration function blocks by using the Application
Configuration tool and the Signal Matrix tool.
Configuring protocol data mapping for IEC 60870-5-101/104, Modbus or
DNP3 with the Communication Management tool.
Configuring the sampled values (process bus) between the devices using
the Application Configuration tool and IEC 61850 Configuration tool.
Record management
Generating overviews on the available (disturbance) recordings in all
connected protection relays by using the Disturbance Handling tool.
Manually reading the recording files (in the COMTRADE format) from the
protection relays by using the Disturbance Handling tool or automatically
by using the PCM600 Scheduler.
Managing recording files with the Disturbance Handling tool.
Relay engineering process
Section 2
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615Relion rec615