10.8

Electromagnetic Compatibility

The SINAMICS G120 drives have been tested in accordance with the EMC Product
Standard EN 61800-3:2004.
Details see declaration of conformity
Note
Install all drives in accordance with the manufacturer's guidelines and in accordance with
good EMC practices.
Use screened cable type CY. Maximal cable length is 15 m.
Table 10- 6
Category C2 - First Environment - Professional Use
Article number
6SL3525-0PE17- . A . 0
6SL3525-0PE21- . A . 0
6SL3525-0PE23- . A . 0
6SL3525-0PE24- . A . 0
6SL3525-0PE25- . A . 0
6SL3525-0PE27- . A . 0
EMC Emissions
Note
Install all drives in accordance with the manufacturer's guidelines and in accordance with
good EMC practices.
Use screened cable type CY. The maximal cable length is 15 m.
Do not exceed the default switching frequency 4 kHz.
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Compliance Table
Remark
All inverters with integrated Class A filters.
The inverter meets the requirements for category C2 for conducted
emissions.
In a domestic environment this product may cause radio interference in
which case supplementary mitigation measures may be required.