Load Monitoring - Siemens Sinamics CU240D-2 DP Operating Instructions Manual

Sinamics g120d distributed inverter control unit with encoder evaluation
Hide thumbs Also See for Sinamics CU240D-2 DP:
Table of Contents

Advertisement

Advanced commissioning
6.21 Monitoring the driven load
6.21.4

Load monitoring

The load monitoring comprises the following components:
● Load failure monitoring
● Monitoring for torque deviation
● Speed deviation monitoring
If the load monitoring detects load failure, the inverter issues fault F07936. For a torque and
speed deviation, as response, you can either set an alarm or a fault. Details are provided in
the following descriptions.
Settings
Table 6- 42
Parameters
p2193
234
Setting options for load monitoring
Description
Load monitoring configuration (factory setting: 1)
0: Monitoring deactivated
1: Torque and load failure monitoring
2: Speed and load failure monitoring
3: Load failure monitoring
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF