If you control the safety functions in the inverter via failsafe digital inputs, then you must
check as to whether the failsafe digital inputs are in some instances interconnected with a
"standard" function.
Procedure
1. Select the screen for the digital inputs.
2. Remove all interconnections of the digital inputs that you use as failsafe digital input F-DI:
3. You must delete the digital input connections for all CDS if you use the switchover of the
command data sets (CDS).
You can find a description of the CDS switchover in the operating instructions.
You have ensured that the failsafe digital inputs only control the safety functions in the
inverter.
❒
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Advanced commissioning
6.11 Safe Torque Off (STO) safety function
161