Advanced commissioning
6.15 Motor control
Parameter
p1562
p1563
p1564
p5310
r5311
p5312
p5313
p5314
p5315
212
Explanation
Moment of inertia estimator change time
load (factory setting: 10 ms)
Moment of inertia estimator load torque positive direction of rotation (factory setting:
0 Nm)
Moment of inertia estimator load torque negative direction of rotation (factory setting:
0 Nm)
Moment of inertia precontrol configuration (factory setting: 0000 bin)
.00 1 signal: Activates calculation of the characteristic (p5312 ... p5315)
.01 1 signal: Activates moment of inertia precontrol
p5310.00 = 0, p5310.01 = 0
p5310.00 = 1, p5310.01 = 0
p5310.00 = 0, p5310.01 = 1
p5310.00 = 1, p5310.01 = 1
Moment of inertia precontrol status word
.00 1 signal: New measuring points for the characteristic of the moment of inertia
precontrol are available
.01 1 signal: New parameters are been calculated
.02 1 signal: Moment of inertia precontrol active
.03 1 signal: The characteristic in the positive direction of rotation has been calculat-
ed and is ready
.04 1 signal: The characteristic in the negative direction of rotation has been calculat-
ed and is ready
.05 1 signal: The inverter writes actual results to the parameter
Moment of inertia precontrol linear positive
(factory setting: 0 1/s
)
2
Moment of inertia precontrol constant
positive (factory setting: 0 kgm
Moment of inertia precontrol linear nega-
tive (factory setting: 0 1/s
2
Moment of inertia precontrol constant
negative (factory setting: 0 kgm
measurements.
The larger p1561 or p1562 is, the more
accurate the results provided by the mo-
ment of inertia estimator.
Deactivating moment of inertia precontrol
Adapting the moment of inertia precontrol
Activating the moment of inertia precontrol.
The characteristic of the moment of inertia pre-
control remains unchanged.
Activating the moment of inertia precontrol. The
inverter adapts the characteristic in parallel.
In a positive direction of rotation:
Moment of inertia = p5312 × load torque +
p5313
)
2
In a negative direction of rotation:
)
Moment of inertia = p5314 × load torque +
p5315
)
2
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF