Table 8- 8
The most important alarms and faults
Number
Cause
F01000
Software error in the CU
F01001
Floating point exception
F01015
Software error in the CU
F01018
Power-up aborted more than once
A01028
Configuration error
F01033
Unit switchover: Reference param-
eter value invalid
F01034
Unit switchover: Calculation of the
parameter values after reference
value change unsuccessful
F01040
Parameters must be saved
F01044
Error loading data from memory
card
A01101
Memory card not available
F01105
CU: Insufficient memory
F01122
Frequency at the probe input too
high
F01205
CU: Time slice overflow
F01250
CU hardware fault
F01512
An attempt has been made to
establish a conversion factor for
scaling which does not exist
A01590
Motor maintenance interval lapsed
F01600
STOP A initiated
F01650
Acceptance test required
F01659
Write task for parameter rejected
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Remedy
Replace CU.
Switch off CU and switch on again.
Upgrade firmware or contact technical support.
1. Switch the module off and on again.
2. After this fault has been output, the module is booted with the factory
settings.
3. Recommission the inverter.
Explanation: The parameter assignments on the memory card were cre-
ated with a different type of module (Article no.).
Check the module parameters and recommission if necessary.
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Select the value of the reference parameter so that the parameters in-
volved can be calculated in the per unit notation (p0304, p0305, p0310,
p0596, p2000, p2001, p2002, p2003, r2004).
Save parameters (p0971).
Switch CU off and on again.
Replace memory card or CU.
Insert a memory card or deactivate the warning A01101.
Activate message for a memory card that is not inserted
(Page 249)
Reduce number of data sets.
Reduce the frequency of the pulses at the probe input.
Contact technical support.
Replace CU.
Create scaling or check transfer value.
Carry out maintenance and reset the maintenance interval (p0651).
Select the STO safety function and then deselect again.
Carry out an acceptance test and create test certificate.
Switch off the Control Unit and switch on again.
Cause: The inverter should be reset to the factory setting. However, it is
not permissible to reset the safety functions as the safety functions are
currently enabled.
Remedy with operator panel:
p0010 = 30
Parameter reset
p9761 = ...
Enter password for the safety functions.
p0970 = 5
Reset start safety parameter.
The inverter sets p0970 = 5 once it has reset the pa-
rameters.
Then reset the inverter to the factory setting again.
Alarms, faults and system messages
8.6 List of alarms and faults