1.13 Compressor Capacity Control

RSXY5K
Pressure is sampled every 20 seconds by pressure sensor, and the inverter compressor is controlled in 13
stages by microcomputer.
Frequency range: 34 - 116 Hz (13 stages) and common for 50/60Hz area.
RSXY8, 10K
<For products produced before July '99>
Pressure is sampled every 20 seconds by two pressure sensors, and the inverter compressor is controlled
in 21 stages by microcomputer. (∗ 20 Stages for products produced after Aug. '99)
Functions Inverter K Series
Min. output
Frequency
30Hz
34Hz
38Hz
42Hz
48Hz
54Hz
60Hz
68Hz
76Hz
86Hz
96Hz
106Hz
116Hz
Max. output
(VE004)
Commercial power supply
Commercial power supply
compressor (off)
compressor (full load)
Frequency
30Hz+OFF
34Hz+OFF
38Hz+OFF
42Hz+OFF
48Hz+OFF
54Hz+OFF
60Hz+OFF
68Hz+OFF
76Hz+OFF
86Hz+OFF
96Hz+OFF
106Hz+OFF
116Hz+OFF
106Hz+ON
116Hz+ON
Min. output
Frequency
38Hz+ON
48Hz+ON
60Hz+ON
76Hz+ON
86Hz+ON
96Hz+ON
Max. output
(VE005)