Daikin VRV Inverter K Series Manual page 351

Table of Contents

Advertisement

SI-05C.BOOK Page 337 Monday, November 6, 2000 4:13 PM
SiE-05C
2.1.2
Setting Mode 2 Pump Down Procedure
Normal mode
Push and hold the Mode
MODE
button (BS1) for 5 seconds.
Setting mode 2
No
Setting item
1
EMG
Pump down
11
operation 1
Pump down
12
operation 2
Pump down
13
operation 3
Pump down operation
The indoor unit will not accept
remote controller operation
when "under centralized
control" is displayed.
Special Service Mode PLUS Series
MODE
LED display
Setting contents
20 21 22 23 24 25 26
Emergency operation when
inverter type outdoor unit
malfunctions
Push
14 times.
SET
Pump down operation
for inverter type
SET
Pump down operation for constant
speed type outdoor unit 1
SET
Pump down operation for constant
speed type outdoor unit 2
R
Mode
Low pressure
display
display
Compressor operation
Mode
Low pressure
display
display
R
or 60 minutes elapse or stop due to malfunction
R
Mode
Low pressure
display
display
(Normal complete)
Pump Down Operation when Replacing The Compressor
MODE
MODE button (BS1)
SET button (BS2)
SET
R
RETURN button (BS3)
Pump down
operation
SET
Normal
operation
R
(When malfunctioning)
Mode
Low pressure
display
display
· Low pressure display
: Low pressure > 3.5k
: Low pressure < 3.5k
: Low pressure < 2.5k
: Low pressure < 1.5k
Mode
Low pressure
display
display
(Stop due to malfunction)
: http://splitoff.ru/tehn-doc.html
(k: kg/cm
2
)
SET
R
(VF167)
337

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rsx5kRsx8kRsx10kVrv plus seriesRsxy5kRsxy10k ... Show all

Table of Contents