SI-05C.BOOK Page 122 Monday, November 6, 2000 4:13 PM
Operation Flowcharts
Option
∗12 Air flow direction
∗13 Hot start
122
Heating operation
Drain kit (M1P): OFF
Swing flap?
∗12
Swing flap
Defrost operation
in progress?
Hot start in progress?
Defrost/Hot start display: OFF
YES
Recycling gurad timer
ON (5 minutes)?
Test run in progress?
∗14
Thermostat status?
Option
Auxiliary electric heater
Auxiliary electric heater
(52H): OFF
(52H): OFF
Humidifier (Hu): OFF
Humidifier (Hu): ON
∗15
Fan M1F : LL operation
Electronic expansion valve
Y1E : capacity contorol
A
Air discharge is 100% horizontal when heating operation is turned off by thermostat.
Hot start is carried out when operation starts or defrosting is complete, and condenser inlet
temperature exceeds 34˚C, or 3 minutes elapses, or when Tc > 52˚C.
NO
∗12
YES
Air flow direction setting
YES
NO
∗13
YES
NO
NO
NO
Option
Auxiliary electric heater
(52H): ON
Humidifier (Hu): ON
Yes
Thermostat status?
NO
Fan M1F : Operating
Fan M1F : L
at set air flow volume
operation
Electronic expansion
valve Y1E
capacity contorol
: http://splitoff.ru/tehn-doc.html
Troubleshooting Inverter K Series
SiE-05C
Defrost/Hot start display: ON
Option
Auxiliary electric heater
(52H): OFF
Humidifier (Hu): OFF
Fan M1F : OFF
Electronic expansion
valve Y1E :open
(VF025)