SI-05C.BOOK Page 89 Monday, November 6, 2000 4:13 PM
SiE-05C

1.15 Remote Controller Self-Diagnosis Function

The remote controller switches are equipped with a self diagnosis function so that more appropriate
maintenance can be carried out. If a malfunction occurs during operation, the operation lamp, malfunction
code and display of malfunctioning unit No. let you know the contents and location of the malfunction.
When there is a stop due to malfunction, the contents of the malfunction given below can be diagnosed by
a combination of operation lamp, INSPECTION display of the liquid crystal display and display of
malfunction code. It also lets you know the unit No. during group control.
Operation lamp
Inspection display
Blinking
Blinking
Blinking
Blinking
On
Off
Blinking
Blinking
Blinking
Blinking
On
Off
Blinking
Blinking
On
Off
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
On
On
Blinking
Blinking
Blinking
Blinking
On
Off
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
On
Off
Blinking
Blinking
Blinking
Blinking
On
Off
Blinking
Blinking
Blinking
Blinking
On
Off
Blinking
Blinking
Test Operation Inverter K Series
Unit No.
Malfunction code
Blinking
A0
Indoor unit: Error of external protection device
Blinking
A1
Indoor unit: Failure of PC board
Blinking
A1
Indoor unit: Failure of PC board
Blinking
A3
Indoor unit: Malfunction of drain level control system (33H)
Blinking
A6
Indoor unit: Fan motor lock
Blinking
A7
Indoor unit: Malfunction of swing flap motor (M1S)
Blinking
A9
Indoor unit: Malfunction of moving part of electronic
expansion valve (Y1E)
Blinking
AF
Indoor unit: Drain level above limit
Blinking
AH
Indoor unit: Malfunction of air filter maintenance
Blinking
AJ
Indoor unit: Malfunction of capacity setting
Blinking
C4
Indoor unit: Malfunction of thermistor (R2T) for liquid pipe
(loose connection, disconnection, short circuit, failure)
Blinking
C5
Indoor unit: Malfunction of thermistor (R3T) for gas pipes
(loose connection, disconnection, short circuit, failure)
Blinking
C9
Indoor unit: Malfunction of thermistor (R1T) for air inlet
(loose connection, disconnection, short circuit, failure)
On
CJ
Indoor unit: Malfunction of thermostat sensor in remote
controller
Blinking
E0
Outdoor unit: Actuation of safety device
Blinking
E1
Outdoor unit: PC board failure
Blinking
E1
Outdoor unit: PC board failure
Blinking
E3
Outdoor unit: Actuation of high pressure switch
Blinking
E4
Outdoor unit: Actuation of low pressure switch
Blinking
E9
Outdoor unit: Malfunction of moving part of electronic
expansion valve (Y1E)
Blinking
F3
Outdoor unit: Abnormal discharge pipe temperature
Blinking
H3
Outdoor unit: High pressure switch failure
Blinking
H4
Outdoor unit: Actuation of low pressure switch
Blinking
H9
Outdoor unit: Malfunction of thermistor (R1T) for outdoor air
(loose connection, disconnection, short circuit, failure)
Blinking
H9
Outdoor unit: Malfunction of thermistor (R1T) for outdoor air
(loose connection, disconnection, short circuit, failure)
Blinking
J1
Outdoor unit: Malfunction of pressure sensor
Blinking
J3
Outdoor unit: Malfunction of discharge pipe thermistor (R3T)
(loose connection, disconnection, short circuit, failure)
Blinking
J3
Outdoor unit: Malfunction of discharge pipe thermistor (R3T)
(loose connection, disconnection, short circuit, failure)
Blinking
J5
Outdoor unit: Malfunction of thermistor (R4T) for suction
pipe (loose connection, disconnection, short circuit, failure)
: http://splitoff.ru/tehn-doc.html