SI-05C.BOOK Page 38 Monday, November 6, 2000 4:13 PM
Functions
Low Outdoor Air
Cooling IN
Conditions (Step 2)
<For products produced after Aug. '99>
38
Normal operation
• Cooling with compressor running
(doesn't include oil return)
&
• High pressure < 7.5 kg/cm²
(0.735 MPa)
&
• Outdoor air temperature < 20˚C
&
• Radiator fin temperature < 60˚C
Normal operation
• Cooling with compressor running
(doesn't include oil return)
&
• High pressure < 7.5 kg/cm²
(0.735 MPa)
&
• Radiator fin temperature < 60˚C
Condition satisfied
• Compressor off
• Other than cooling (includes oil return)
• High pressure > 15.8 kg/cm²
• Outdoor air temperature > 25˚C
• Radiator fin temperature > 80˚C
Conditions satisfied
Condition satisfied
• Compressor off
• Other than cooling (includes oil return)
• High pressure > 15.8 kg/cm²
• Radiator fin temperature > 80˚C
Conditions satisfied
: http://splitoff.ru/tehn-doc.html
SiE-05C
or
or
(1.548 MPa)
or
or
Step 2
(VF007-1)
or
or
(1.548 MPa)
or
Step 2
(VF007-2)