SI-05C.BOOK Page 293 Monday, November 6, 2000 4:13 PM
SiE-05C
1.8.4
Setting of Cool/Heat by Outdoor Unit System Group in Accordance with Group Master
Outdoor Unit by COOL/HEAT Selector Remote Controller
Test Operation PLUS Series
Install the External control adaptor for outdoor unit on either the outdoor - outdoor, indoor - outdoor, or
indoor - indoor transmission line.
Set SS1 of the outdoor unit PCB to "OUT/DOOR UNIT" (factory set).
In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as the group
master, and set the other outdoor units as group slave units.
: http://splitoff.ru/tehn-doc.html
Test Operation
293