Daikin VRV Inverter K Series Manual page 104

Table of Contents

Advertisement

SI-05C.BOOK Page 90 Monday, November 6, 2000 4:13 PM
Test Operation
Operation lamp
Inspection display
Blinking
Blinking
On
Off
Blinking
Blinking
Blinking
Blinking
On
Off
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Off
Blinking
Blinking
Blinking
Blinking
On
Off
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
Off
On
Blinking
Blinking
On
Off
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
On
On
Blinking
Blinking
Blinking
Blinking
Blinking
Blinking
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
90
Unit No.
Malfunction code
Blinking
J6
Outdoor unit: Malfunction of thermistor (R2T) for heat
exchanger (loose connection, disconnection, short circuit,
failure)
Blinking
J6
Outdoor unit: Malfunction of thermistor (R2T) for heat
exchanger (loose connection, disconnection, short circuit,
failure)
Blinking
JA
Outdoor unit: Malfunction of discharge pipe pressure sensor
Blinking
JC
Outdoor unit: Malfunction of suction pipe pressure sensor
Blinking
JH
Outdoor unit: Malfunction of oil temperature sensor
Blinking
L0
Outdoor unit: Failure of inverter system
Blinking
L4
Outdoor unit: Failure of inverter cooling
Blinking
L5
Outdoor unit: Compressor motor insulation defect, short
circuit, power unit short circuit
Blinking
L6
Outdoor unit: Compressor motor insulation defect, short
circuit
Blinking
L8
Outdoor unit: Compressor overload, compressor motor wire
cut
Blinking
L9
Outdoor unit: Compressor lock
Blinking
LA
Outdoor unit: Malfunction of power unit
Blinking
LC
Outdoor unit: Malfunction of transmission between inverter
and outdoor control unit
Blinking
PO
Gas depletion (heat build up)
Blinking
P1
Outdoor unit: Power supply voltage imbalance, open phase
Blinking
P4
Outdoor unit: Malfunction of power unit temperature sensor
Blinking
U0
Refrigerant shortage, low pressure drop due to failure of
electronic expansion valve
Blinking
U1
Negative phase / open phase
Blinking
U2
Power supply insufficient or instantaneous failure
Blinking
U4
Malfunction of transmission between indoor unit and
outdoor unit / BS unit, or outdoor unit and BS unit
Blinking
U5
Malfunction of transmission between remote controller and
indoor unit
Off
U5
Failure of remote controller PC board or setting during
control by remote controller
Blinking
U7
Malfunction of transmission between indoor units
Malfunction of transmission between outdoor units,
malfunction of transmission between outdoor unit and ice
build-up heat unit
Blinking
U7
Malfunction of transmission between outdoor units (cool/
heat unified, low noise)
Off
U8
Malfunction of transmission between main remote controller
and sub remote controller (malfunction of slave remote
controller)
Blinking
U9
Malfunction of transmission between indoor unit and
outdoor unit in same system
between BS unit and indoor/outdoor unit in same system
Blinking
UA
Failure of combination of indoor / BS / outdoor units (model,
No. of units, etc.)
remote controller (applicable remote controller)
BS unit connection position
On
UC
Address duplication of central remote controller
Blinking
UE
Malfunction of transmission between indoor unit and central
remote controller
Blinking
UF
System not set
Blinking
UH
Failure of system
: http://splitoff.ru/tehn-doc.html
SiE-05C
Malfunction contents
Malfunction of transmission
Failure of combination of indoor unit and
Failure of
Test Operation Inverter K Series