SI-05C.BOOK Page 289 Monday, November 6, 2000 4:13 PM
SiE-05C
[Common]
Decide the address for each control unit from 0~9 and set.
Input signal
Constant contact a
Input current is approx. 12 - 24 VDC, 10 mA per contact.
Use a micro-current contact for the relay contact.
(Max. 12 VDC, 1 mA)
Outside wiring specifications
Recommended electric wiring: Sheathed vinyl cord or cable 0.75~1.25 mm² (double core)
Wiring length: Max. 150 m
Run separate from power line in order to prevent malfunction.
Note:
Be sure to make the address No. of the PC board adaptor described above match the address No. of
function unit or outdoor unit (BS unit if using heat recovery type).
(For detailed settings, see the installation manual.)
Refer to the INSTALLATION INSTRUCTION
Test Operation PLUS Series
Address Setting (DS1 / DS2)
Control Input Specifications
: http://splitoff.ru/tehn-doc.html
Test Operation
289