SI-05C.BOOK Page 225 Monday, November 6, 2000 4:13 PM
SiE-05C
4.3
Oil Return Control
In order to recover refrigeration oil, when total compressor operation capacity equals the reference values,
the capacity is increased, all solenoid valves in the system are fully opened and the oil is recovered at each
compressor.
4.3.1
Conditions for Executing Oil Control
Total compressor operating time = point when approx. 8 hours elapses (Differs somewhat according to
operation status.)
<Heat Pump System>
Operating contents
When cooling
When heating
1 minute
elapses
Preparation
for oil return
Upper limit frequency
limited to 38 Hz + ON
Liquid refrigerant collected in
indoor unit returned to receiver
Functions PLUS Series
Step 1: Collected oil is recovered.
INV outdoor unit
STD outdoor unit 1
Compressor
(106Hz + ON)
+
EEV
2000pls
Outdoor unit fan
H + ON
Outdoor unit heat exchanger
Condenser
Solenoid valve for oil discharge
Injection
ON + OFF
Hot gas
Outdoor unit suction pipe temp. ≤ Te + 10˚C
at when either 6 min. or 4 min. elapses.
Step 2: Refrigerant is discharged from accumulator.
INV outdoor unit
STD outdoor unit 1
Compressor
(60Hz + ON)
+
EEV
Outdoor unit fan
H + ON
Outdoor unit heat exchanger
Condenser
Solenoid valve for oil discharge
Injection
ON + OFF
Hot gas
ON at Lp < 1.0 k
Step 1: 4-way valve switched (30 sec. after start)
INV outdoor unit
STD outdoor unit 1
Compressor
(38Hz + ON)
+
EEV
2000pls
Outdoor unit fan
H + ON
Outdoor unit heat exchanger
Condenser
Solenoid valve for oil discharge
Injection
ON + OFF
Hot gas
30 seconds elapse
Step 2: Collected oil is recovered.
INV outdoor unit
STD outdoor unit 1
Compressor
(106Hz + ON)
+
EEV
2000pls
Outdoor unit fan
H + ON
Outdoor unit heat exchanger
Condenser
Solenoid valve for oil discharge
Injection
ON + OFF
Hot gas
Outdoor unit suction pipe temp. ≤ Te + 10˚C
at when either 6 min. or 4 min. elapses.
Step 3: Refrigerant is discharged from accumulator. (3 minutes)
INV outdoor unit
STD outdoor unit 1
Compressor
(60Hz + OFF)
+
EEV
Outdoor unit fan
H + ON
Outdoor unit heat exchanger
Evaporator
Solenoid valve for oil discharge
Injection
ON + OFF
Hot gas
ON at Lp < 2.5 k
STD outdoor unit 2
(ON + ON)
+
(ON + ON)
2000pls
2000pls
H + ON
H + ON
Condenser
Condenser
OFF
ON + OFF
ON + OFF
OFF
STD outdoor unit 2
(ON + OFF)
+
(ON + OFF)
SH control
H + ON
H + ON
Condenser
Condenser
ON
ON + OFF
ON + OFF
STD outdoor unit 2
(ON + OFF)
+
(ON + OFF)
2000pls
2000pls
H + ON
H + ON
Condenser
Condenser
ON
ON + OFF
ON + OFF
ON
STD outdoor unit 2
(ON + ON)
+
(ON + ON)
2000pls
2000pls
H + ON
H + ON
Condenser
Condenser
ON
ON + OFF
ON + OFF
OFF
STD outdoor unit 2
(ON + OFF)
+
(ON + OFF )
SH control
H + ON
H + ON
Evaporator
Evaporator
OFF
ON + OFF
ON + OFF
: http://splitoff.ru/tehn-doc.html
Outline of Control
2
(k:kg/cm
)
3 minutes elapses
or suction
pressure < 1.0
Quit
3 minutes
elapses or
HP > 21k
Quit
(VF107)
225