1.20 Unified ON/OFF Controller (DCS301A51/ DCS301B61)
Turns each group of indoor units on/off individually or simultaneously for up to 16 groups (128 units), and
lets you check the operation/malfunction display all at once at a glance.
1.20.1 System Configuration
Up to 16 groups of indoor units can be turned on/off individually or simultaneously by unified ON/OFF
controller. Also lets you connect with an outside key system or host computer monitor panel by forced OFF
input (no-voltage a contact).
(This optional accessory cannot be used in combination with optional accessory wiring adaptor for
electrical appendices.)
Test Operation Inverter K Series
Lets you turn up to 16 groups of indoor units (128 units) on/off simultaneously or individually, and lets
you check the operation/malfunction display all at once at a glance.
By combining with a central remote controller or schedule timer, you can build a system that matches
scale and use .
Features compact size casing with thickness of only 16 mm. (Uses JIS recessed box for 2)
Wiring can be extended up to 1 km. For the wiring method, bus type and star type wiring crossover
wiring can be used as well as crossover wiring.
Can be used in combination with other D-BACS equipment.