SI-05C.BOOK Page 333 Monday, November 6, 2000 4:13 PM
SiE-05C
Malfunctions for
which Backup
Operation can or
cannot Be
Tripped Safety Device
Executed
Faulty PC Board
Tripped LPS
Solenoid Valve Malfunction
Discharge Pipe
Temperature Malfunction
Faulty Control HPS
Faulty Control LPS
Air Thermistor Malfunction
Discharge Pipe Thermistor
Malfunction
Suction Pipe Thermistor
Malfunction
Heat Exchange Thermistor
Malfunction
Oil Temperature Thermistor
Malfunction
Header Thermistor
Malfunction
Reverse Phase / Negative
Phase
Outdoor - L Transmission
Malfunction
Special Service Mode PLUS Series
Malfunction
Malfunction Code
E0
E1
E4
E9
F3
H3
H4
H9
J3
J5
J6
JH
J7
U1
U7
Backup and Emergency Operation
PC Board Type
EB9446~9A
EB9446~9B (Applies to items
manufactured from June on.)
Cannot Operate
Cannot Operate
Cannot Operate
Cannot Operate
Cannot Operate
Cannot Operate
Cannot Operate
Can Operate
Cannot Operate
Can Operate
Can Operate
Can Operate
Can Operate
Cannot Operate
Cannot Operate
: http://splitoff.ru/tehn-doc.html
Can Operate
Cannot Operate
Can Operate
Can Operate
Can Operate
Cannot Operate
Cannot Operate
Can Operate
Can Operate
Can Operate
Can Operate
Can Operate
Can Operate
Cannot Operate
Cannot Operate
333