Wiring Adaptor
Common Address
Decide the address for each control unit from 0~9 and set.
Setting (DS1 / DS2)
Note:
1. Setting is within 8 groups when using a cool/heat central remote controller. Set from No. 0~No. 7.
2. Be sure to make the address No. of the PC board adaptor described above match the address No. of
Refer to the INSTALLATION INSTRUCTION.
Common Control
Input
Specifications
386
function unit or outdoor unit (BS unit if using cool/heat simultaneous selection type).
(For detailed settings, see the installation manual.)
Input signal
Constant contact a
Input current is approx. 12 - 24 VDC, 10 mA per contact.
Use a micro-current contact for the relay contact.
(Max. 12 VDC, 1 mA)
Outside wiring specifications
Recommended electric wiring: Sheathed vinyl cord or cable 0.75~1.25 mm² (double core)
Wiring length: Max. 150 m
Run separate from power line in order to prevent malfunction.