SI-05C.BOOK Page 154 Monday, November 6, 2000 4:13 PM
Troubleshooting
3.31 Malfunction of Transmission Between Master and Slave Remote Controllers
U U U U 8 8 8 8
Remote Controller
Display
Supposed Causes
Troubleshooting
154
Malfunction of transmission between main and sub remote controller
Connection between sub remote controllers
Defect of remote controller PC board
NO
Using 2-remote controllers
control.
YES
SS1
NO
of both remote controllers is set
to "SUB."
YES
SS1
NO
of remote controller PC boards
Set SS1 to "MAIN"; the power
is set to "MAIN."
supply off once and then back on.
YES
Turn the power off and then back
on. If a malfunction occurs,
replace the remote controller PC
board.
Set one remote controller to
"MAIN"; the power supply off once
and then back on.