Daikin VRV Inverter K Series Manual page 384

Table of Contents

Advertisement

SI-05C.BOOK Page 370 Monday, November 6, 2000 4:13 PM
Wiring Adaptor
5.1.2
Wiring
Operation Signal
Control Mode
Display Signal
Fetch
Note:
370
Combined use of constant contact (a) and instantaneous contact (a)
Combined use of voltage 12~24 VDC, no valtage
Remote control mode selector switch (Control contents differ according to input mode. See the
following page for details.)
Display of malfunction signal (no voltage contact [a])
Display of operation (no voltage contact [a])
Remote temperature setting (Can be set from 16~32˚C.)
For voltage input, approximately 10 mA of input current per contact is required.
In the case of input, use a micro-current contact as the input contact.
There is no polarity for valtage input.
Either plus common or minus common can be used for terminal BC.
Temperature input is resistance value input of 0~135
.