Daikin VRV Inverter K Series Manual page 48

Table of Contents

Advertisement

SI-05C.BOOK Page 34 Monday, November 6, 2000 4:13 PM
Functions
Outdoor Unit
Function
Notes
34
Outdoor air (R1T)
Compressor
INV
R1T < -10˚C
86Hz
-10˚C ≤ R1T < 0˚C
76Hz
R1T ≥ 0˚C
60Hz
Compressor upper limit is 116Hz+OFF for 10 minutes of next start after entering residual operation.
(∗ Except for products produced after Aug. '99.)
During defrost or oil return, residual operation is not carried out even if a stop command comes.
Forced thermostat OFF occurs if defrost or oil return signal comes during residual operation.
Electronic
Pressure equalizing
expansion valve
solenoid valve
STD
OFF
0~300 pulses
ON or OFF
OFF
0~300 pulses
ON or OFF
OFF
0~300 pulses
ON or OFF