SI-05C.BOOK Page 385 Monday, November 6, 2000 4:13 PM
SiE-05C
<Settings of
Switches on The
PC Board Adaptor>
Note:
For PLUS Series
Set the SS1 cool/heat selector switch on the function unit to "outdoor." You must also set cool/heat selector
"master" or "slave" by pushbutton switch.
5.6.3
Demand / Low Noise Control
Connecting control input to the adaptor for outside control of outdoor units enables demand and low noise
control.
Demand Control
When short circuit between (1) and (C): Approx. 70% as a guideline
(Figures Indicate
When short circuit between (2) and (C): Approx. 40% as a guideline
Demand Rate)
When short circuit between (3) and (C): Forced fan operation
Low Noise Control
Running noise can be reduced by 2~3dB by controlling capacity of outdoor unit.
(Outdoor Unit)
<System Outline>
Appendix Inverter K Series / PLUS Series
: http://splitoff.ru/tehn-doc.html
Wiring Adaptor
385