Daikin VRV Inverter K Series Manual page 194

Table of Contents

Advertisement

SI-05C.BOOK Page 180 Monday, November 6, 2000 4:13 PM
Troubleshooting (OP: Unified ON/OFF Controller)
8.3
Display "Under Host Computer Integrate Control" Blinks (Repeats Double
Blink)
Remote Controller
"under host computer integrated control" (Repeats double blink)
Display
Supposed Causes
Troubleshooting
180
Central control address (group No.) is not set for indoor unit.
Improper address setting
Improper wiring of transmission wiring
Is the central
NO
control address (group No.) set
for the indoor unit?
YES
Is the switch
NO
for setting each address set
correctly?
YES
Is
the transmission
NO
wiring disconnected or wired
incorrectly?
YES
Replace the PC board of the unified
ON/OFF controller.
Set by remote controller the central
control address for all indoor units
connected to the central control line.
Set the switch for setting each address
correctly and simultaneously reset the
power supply for all optional controllers
for centralized control.
Fix the wiring correctly.
: http://splitoff.ru/tehn-doc.html
Troubleshooting Inverter K Series
SiE-05C
(VF082)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rsx5kRsx8kRsx10kVrv plus seriesRsxy5kRsxy10k ... Show all

Table of Contents