SI-05C.BOOK Page 283 Monday, November 6, 2000 4:13 PM
SiE-05C
No Setting item
Description
1
EMG
Emergency operation
(Emergency
when Inverter type
operation 1)
outdoor unit malfunctions.
S
2
Cool/heat
Address for cool/heat
unified
unified operation
address
S
3
Low noise /
Address for low noise
demand
/ demand operation
address
S
4
Forced fan
Indoor unit fan turns
switch
while unit is stopped.
S
5
Indoor unit
Allows operation of
forced
indoor unit from
operation
outdoor unit
S
Fixes compressor frequency.
6
Frequency fix
INV : (60Hz + OFF)
STD 1 : (ON+OFF)
STD 2 : (ON+OFF)
S
7
TE setting
Low pressure setting
for cooling
S
8
TC setting
High pressure setting
Note 1
for heating
S
9
Defrost
Temperature setting
setting
for defrost
Note 1
S
10
Air Net
Address for
address
Air Net
S
11
Pump down
Pump down operation
operation 1
of INV outdoor unit
S
12
Pump down
Pump down operation
operation 2
of STD 1 outdoor unit
S
13
Pump down
Pump down operation
operation 3
of STD 2 outdoor unit
S
14
Forced back
Executes emergency
up operation
operation when
(Emergency
constant speed
operation 2)
outdoor unit is faulty.
S
Initial setting (EMG)
Test Operation PLUS Series
LED display
H1P H2P H3P H4P H5P H6P H7P
Emergency operation
R
Normal operation
Address
Binary number
R
(6 digits)
Address
Binary number
R
(6 digits)
Forced fan operation
(H tap)
R
Normal operation
Push 3 times
Forced fan operation
(H tap)
R
Normal operation
Frequency fix
R
Normal operation
High
R
Normal (factory set)
Low
R
Push 3 times
Quick defrost
R
Normal (factory set)
Slow defrost
Address
Binary number
R
(6 digits)
Pump down
operation
R
Normal operation
Push 4 times
Constant speed outdoor
unit 2 has broken
Constant speed outdoor
R
unit 1 has broken
Normal operation
LED display
LED display
H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
R
S
0
S
1
S
R
S
2
S
31
0
S
1
R
S
S
2
S
31
S
R
S
R
S
R
S
S
R
S
S
R
S
S
0
S
1
R
S
S
2
S
63
S
R
S
S
R
S
RETURN BUTTON
R
SET BUTTON
S
: http://splitoff.ru/tehn-doc.html
Test Operation
R
R
R
R
R
R
R
R
R
R
R
(VF134)
283