SI-05C.BOOK Page 375 Monday, November 6, 2000 4:13 PM
SiE-05C
Position
Note:
Forced off (disregard input A) is effected when using input B constant input at positions 7~A. Input B
constant input cannot be used by B.
Appendix Inverter K Series / PLUS Series
Remote control mode selector switch (RS1) setting
Function
0
Disregard input
1
Remote controller
Operates by ON and stops by OFF
inhibited
2
Central priority
Operates by ON (remote controller
permitted) and stops by OFF (remote
controller inhibited)
3
Remote controller
Same as mode 1 (OFF by remote
permitted / inhibited
controller always permitted)
4
Remote controller
ON by remote controller permitted, stops
permitted / inhibited /
by OFF (remote controller inhibited)
OFF
5
Remote controller
ON / OFF (cyclic)
inhibited
6
Individual
Same as mode 5 (only OFF by remote
controller always permitted)
7
Remote controller
Operates by ON
inhibited
8
Central priority
Operates by ON (remote controller
permitted)
9
OFF by remote controller
Same as mode 7 (OFF by remote
permitted
controller always permitted)
A
Remote controller
ON by remote controller permitted
permitted / inhibited /
OFF
B
Individual
Same as mode 7 (remote controller
always permitted)
C
Mode 5 + energy
Same as mode 5
efficiency control
D
Mode 5 + room
temperature setting shift
E
Mode 6 + energy
Same as mode 6
efficiency control
F
Mode 6 + room
temperature setting shift
Example of when the remote control selector switch (RS1) is set to No. 6
Below are remote control commands relative to input signal and indoor unit time chart
Operation by input mode A and B
Input A (between B1~Bc)
: http://splitoff.ru/tehn-doc.html
Wiring Adaptor
Input B (between B2~Bc)
Stops by ON, remote controller
inhibited Disregard input A Input
A permitted by OFF
"Stops by ON, remote controller
inhibited Remote controller
permitted by OFF
Stops by ON
Inhibited by ON (remote
controller inhibited)
Same as mode 7
Remote controller inhibited by
ON
Same as mode 7
Forced OFF by thermostat by
ON
Room temperature shift
operation by ON
Forced OFF by thermostat by
ON
Room temperature shift
operation by ON
375