SiUS28-902_a
5. Troubleshooting by Indication on the Unified ON/
OFF Controller
5.1
Operation Lamp Blinks
Remote
Operation lamp blinks
Controller
Display
Applicable
All models of indoor units
Models
Unified ON/OFF controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Malfunction of transmission between optional controller and indoor unit
Supposed
Connector for setting master controller is disconnected
Causes
Defect of unified ON/OFF controller
Defect of indoor unit P.C.B.
Malfunction of air conditioner
Troubleshooting
Troubleshooting by Indication on the Unified ON/OFF Controller
150