Specifications
7.1.5 Line Power Supply 3x525–600 V AC
Type designation
High/normal overload
Typical shaft output [kW]
Typical shaft output [hp]
Protection rating IP20/Chassis
Protection rating IP21/Type 1
Protection rating IP55/Type 12
Output current
Continuous (3x525–550 V) [A]
Intermittent (3x525–550 V) [A]
Continuous (3x551–600 V) [A]
Intermittent (3x551–600 V) [A]
Continuous kVA at 550 V [kVA]
7
7
Continuous kVA at 550 V [kVA]
Maximum input current
Continuous (3x525–600 V) [A]
Intermittent (3x525–600 V) [A]
Maximum pre-fuses [A]
Additional specifications
Maximum cable cross-section
power, motor, brake, and load sharing
2
[mm
] ([AWG])
Maximum cable cross-section
power disconnect [mm
Estimated power loss
at rated maximum load [W]
Efficiency
5)
Table 7.11 Line Power Supply 3x525–600 V AC, PK75–P2K2
158
®
VLT
PK75
1)
HO
0.75
1
A3
A5
1.8
2.7
1.7
2.6
1.7
1.7
1.7
2.6
10
2)
for line
2)
for line
2
] ([AWG])
3)
35
4)
0.97
Danfoss A/S © 09/2014 All rights reserved.
AQUA Drive FC 202
P1K1
NO
HO
NO
1.1
1.5
A3
A5
2.6
2.0
3.9
2.9
2.4
1.9
3.6
2.6
2.5
2.4
2.4
1.9
3.6
2.6
10
4,4,4 (12,12,12)
(minimum 0.2 (24))
6,4,4 (10,12,12)
50
0.97
P1K5
P2K2
HO
NO
HO
1.5
2.2
2
A3
A3
A5
A5
2.9
4.1
4.4
3.2
6.2
2.7
3.9
4.1
3.0
5.9
2.8
3.9
2.7
3.9
2.7
4.1
4.1
3.0
6.2
10
20
65
92
0.97
0.97
NO
3
4.5
4.3
4.5
MG20N622