Danfoss VLT AQUA Drive FC 202 Design Manual page 73

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

System Integration
2 digital outputs NPN/PNP push pull
1 analog output 0/4–20 mA
Spring-loaded connection
Separate parameter settings Ordering number
130B1125 uncoated – 130B1212 coated (Class
G3/ISA S71.04-1985)
Relay option MCB 105
Enables to extend relay functions with three additional
relay outputs.
Maximum terminal load: AC-1 resistive load: 240
V AC 2 A AC-15
Inductive load @cos ф 0.4: 240 V AC 0.2 A DC-1
Resistive load: 24 V DC 1 A DC-13
Inductive load: @cos ф 0.4: 24 V DC 0.1 A
Minimum terminal load: DC 5 V: 10 mA
Maximum switch rate at rated load/min. load: 6
min-1/20 s-1
Ordering number 130B1110 uncoated–130B1210
coated (Class G3/ISA S71.04-1985)
Analog I/O option MCB 109
This analog input/output option is easily fitted in the
adjustable frequency drive for upgrading to advanced
performance and control using the additional inputs/
outputs. This option also upgrades the adjustable
frequency drive with a battery backup supply for the clock
built into the adjustable frequency drive. This provides
stable use of all adjustable frequency drive clock functions
as timed actions.
Three analog inputs, each configurable as both
voltage and temperature input.
Connection of 0–10 V analog signals as well as
PT1000 and NI1000 temperature inputs.
3 analog outputs each configurable as 0–10 V
outputs.
Included backup supply for the standard clock
function in the adjustable frequency drive. The
backup battery typically lasts for 10 years,
depending on environment. Ordering number
130B1143 uncoated – 130B1243 coated (Class
G3/ISA S71.04-1985).
PTC thermistor card MCB 112
With the MCB 112 PTC thermistor card, all Danfoss
adjustable frequency drives with STO can be used to
supervise motors in potentially explosive atmospheres.
MCB 112 offers superior performance compared to the
built-in ETR function and thermistor terminal.
MG20N622
Design Guide
Sensor input card MCB 114
The option protects the motor from being overheated by
monitoring the bearings and windings temperature in the
motor. The limits, as well as the action, are adjustable and
the individual sensor temperature is visible as a read out in
the display or by serial communication bus.
Extended cascade controller MCO 101
Easily fitted and upgrades the built-in cascade controller to
operate more pumps and more advanced pump control in
master/slave mode.
Extended relay card MCB 113
The extended relay card MCB 113 adds inputs/outputs to
®
VLT
AQUA Drive for increased flexibility.
MCO 102 advanced cascade controller
Extends the capabilities of the standard cascade controller
built into adjustable frequency drives.
Danfoss A/S © 09/2014 All rights reserved.
Protects the motor from overheating.
ATEX-approved for use with EX d and EX e
motors.
Uses the safe torque off function of Danfoss
adjustable frequency drives to stop the motor in
case of overtemperature.
Certified for use to protect motors in zones 1, 2,
21, and 22.
Certified up to SIL2.
Protects the motor from overheating.
Three self-detecting sensor inputs for two or
three wire PT100/PT1000 sensors.
One additional analog input 4–20 mA.
Up to six pumps in standard cascade set-up
Up to six pumps in master/slave set-up
Technical specification: See MCB 105 relay option
7 digital inputs: 0–24 V
2 analog outputs: 0/4–20 mA
4 SPDT relays
Rating of load relays: 240 V AC/2 A (Ohm)
Meets NAMUR recommendations
Galvanic isolation capability Ordering number
130B1164 uncoated – 130B1264 coated (Class
G3/ISA S71.04-1985)
Provides eight additional relays for staging of
additional motors.
Provides accurate flow, pressure, and level control
for optimizing the efficiency of systems that use
multiple pumps or blowers.
3
3
71