Danfoss VLT AQUA Drive FC 202 Design Manual page 173

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
7.7.1 CE Compliance
200–240 V, Enclosure sizes A, B, and C
Enclosure
Power [kW (hp)]
A2
0.25–2.2 (0.34–3)
A3
3.0–3.7 (4–5)
A4
0.25–2.2 (0.34–3)
A5
0.25–3.7 (0.34–5)
B1
5.5–11 (7.5–15)
B2
15 (20)
B3
5.5–11 (7.5–15)
B4
15–18
C1
18.5–30 (25–40)
C2
37–45 (50–60)
C3
22–30 (30–40)
C4
37–45 (50–60)
Table 7.19 200–240 V, Enclosure Sizes A, B, and C
MG20N622
Design Guide
Recommended
Recommended
fuse size
maximum fuse
gG-10 (0.25–1.5)
gG-16 (2.2)
gG-16 (3)
gG-20 (3.7)
gG-10 (0.25–1.5)
gG-16 (2.2)
gG-10 (0.25–1.5)
gG-16 (2.2–3)
gG-20 (3.7)
gG-25 (5.5)
gG-32 (7.5)
gG-50
gG-25
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-63 (15)
gG-160 (15–18.5)
gG-80 (18.5)
aR-160 (22)
gG-100 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
gG-80 (18.5)
gG-150 (18.5)
aR-125 (22)
aR-160 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
Danfoss A/S © 09/2014 All rights reserved.
Recommended circuit
breaker
Moeller
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-63
PKZM4-50
gG-125
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
Maximum trip level
[A]
25
25
25
25
7
63
100
50
100
160
250
150
250
171
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents