Danfoss VLT AQUA Drive FC 202 Design Manual page 92

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

System Integration
Coil
Description
number
3
3
1–16
Adjustable frequency drive control
word.
17–32
Adjustable frequency drive speed or
setpoint reference range 0x0–0xFFFF
(-200% ... ~200%).
33–48
Adjustable frequency drive status
word (see Table 3.38)
49–64
Open-loop mode: Adjustable
frequency drive output frequency.
Closed-loop mode: Adjustable
frequency drive feedback signal.
65
Parameter write control (master to
slave)
0
=
1
=
66-65536 Reserved
Table 3.36 Coil Descriptions
Coil
0
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
04
Coast stop
05
Quick stop
06
Freeze freq.
07
Ramp stop
08
No reset
09
No jog
10
Ramp 1
11
Data not valid
12
Relay 1 off
13
Relay 2 off
14
Set up LSB
15
Set up MSB
16
No reversing
Table 3.37 Adjustable Frequency Drive Control Word (FC
Profile)
90
Parameter changes are written to
the RAM of the adjustable
frequency drive.
Parameter changes are written to
the RAM and EEPROM of the
adjustable frequency drive.
1
No DC brake
No coast stop
No quick stop
No freeze freq.
Start
Reset
Jog
Ramp 2
Data valid
Relay 1 on
Relay 2 on
Reversing
Danfoss A/S © 09/2014 All rights reserved.
®
VLT
AQUA Drive FC 202
Signal
Coil
direction
33
34
35
Master to slave
36
37
Master to slave
38
39
40
Slave to master
41
42
Slave to master
43
44
45
46
Master to slave
47
48
Table 3.38 Adjustable Frequency Drive Status Word (FC Profile)
Register
number
00001-00006
00007
00008
00009
00010-00990
01000-01990
02000-02990
03000-03990
04000-04990
...
49000-49990
50000
50010
...
50200
50210
Table 3.39 Holding Registers
1) Used to specify the index number to be used when accessing an
indexed parameter.
0
1
Control not ready
Control ready
Adjustable frequency drive
Adjustable frequency drive
not ready
ready
Coasting stop
Safety closed
No alarm
Alarm
Not used
Not used
Not used
Not used
Not used
Not used
No warning
Warning
Not at reference
At reference
Hand mode
Auto mode
Out of frequency range
In frequency range
Stopped
Running
Not used
Not used
No voltage warning
Voltage warning
Not in current limit
Current limit
No thermal warning
Thermal warning
Description
Reserved
Last error code from an FC data object interface
Reserved
1)
Parameter index
000 parameter group (parameters 0-01 through
0-99)
100 parameter group (parameters 1-00 through
1-99)
200 parameter group (parameters 2-00 through
2-99)
300 parameter group (parameters 3-00 through
3-99)
400 parameter group (parameters 4-00 through
4-99)
...
4900 parameter group (parameters 49-00 through
49-99)
Input data: Adjustable frequency drive control
word register (CTW).
Input data: Bus reference register (REF).
...
Output data: Adjustable frequency drive status
word register (STW).
Output data: Adjustable frequency drive main
actual value register (MAV).
MG20N622