System Integration
3.8.12.2 Status Word According to FC
Profile (STW) (8-10 Control
Profile=FC profile)
3
3
Follower-master
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
no.:
Figure 3.57 Status Word
Bit
Bit=0
00
Control not ready
01
Drive not ready
02
Coasting
03
No error
04
No error
05
Reserved
06
No error
07
No warning
08
Speed ≠ reference
09
Local operation
10
Out of frequency limit
11
No operation
12
Drive OK
13
Voltage OK
14
Torque OK
15
Timer OK
Table 3.46 Status Word Bits
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00=0: The adjustable frequency drive trips.
Bit 00=1: The adjustable frequency drive controls are ready,
but the power component does not necessarily receive any
power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready
Bit 01=1: The adjustable frequency drive is ready for
operation, but the coasting command is active via the
digital inputs or via serial communication.
Bit 02, Coasting stop
Bit 02=0: The adjustable frequency drive releases the
motor.
Bit 02=1: The adjustable frequency drive starts the motor
with a start command.
Bit 03, No error/trip
Bit 03=0: The adjustable frequency drive is not in fault
mode.
94
STW
Output freq.
Bit=1
Control ready
Drive ready
Enable
Trip
Error (no trip)
-
Trip lock
Warning
Speed = reference
Bus control
Frequency limit OK
In operation
Stopped, auto-start
Voltage exceeded
Torque exceeded
Timer exceeded
Danfoss A/S © 09/2014 All rights reserved.
®
VLT
AQUA Drive FC 202
Bit 03=1: The adjustable frequency drive trips. To re-
establish operation, enter [Reset].
Bit 04, No error/error (no trip)
Bit 04=0: The adjustable frequency drive is not in fault
mode.
Bit 04=1: The adjustable frequency drive shows an error
but does not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06=0: The adjustable frequency drive is not in fault
mode.
Bit 06=1: The adjustable frequency drive is tripped and
locked.
Bit 07, No warning/warning
Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
Bit 08, Speed≠reference/speed=reference
Bit 08=0: The motor is running, but the present speed is
different from the preset speed reference. It might, for
example, be the case when the speed ramps up/down
during start/stop.
Bit 08=1: The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09=0: [Stop/Reset] is activated on the control unit or
Local control in 3-13 Reference Site is selected. Control via
serial communication is not possible.
Bit 09=1 It is possible to control the adjustable frequency
drive via the serial communication bus/serial communi-
cation.
Bit 10, Out of frequency limit
Bit 10=0: The output frequency has reached the value in
4-11 Motor Speed Low Limit [RPM] or 4-13 Motor Speed High
Limit [RPM].
Bit 10=1: The output frequency is within the defined limits.
Bit 11, No operation/in operation
Bit 11=0: The motor is not running.
Bit 11=1: The adjustable frequency drive has a start signal,
or the output frequency is greater than 0 Hz.
Bit 12, Drive OK/stopped, autostart
Bit 12=0: There is no temporary overtemperature on the
inverter.
Bit 12=1: The inverter stops because of overtemperature,
but the unit does not trip and resumes operation once the
overtemperature stops.
Bit 13, Voltage OK/limit exceeded
Bit 13=0: There are no voltage warnings.
Bit 13=1: The DC voltage in the adjustable frequency
drive's intermediate circuit is too low or too high.
MG20N622