Danfoss VLT AQUA Drive FC 202 Design Manual page 185

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
36
240
0.244
136
240
0.560
150
240
0.720
Table 7.37 Adjustable Frequency Drive, P22K, T2
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
15
240
0.194
50
240
0.252
150
240
0.444
Table 7.38 Adjustable Frequency Drive, P30K, T2
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
30
240
0.300
100
240
0.536
150
240
0.776
Table 7.39 Adjustable Frequency Drive, P37K, T2
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
30
240
0.300
100
240
0.536
150
240
0.776
Table 7.40 Adjustable Frequency Drive, P45K, T2
380–480 V (T4)
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
5
400
0.640
50
400
0.470
150
400
0.760
Table 7.41 Adjustable Frequency Drive, P1K5, T4
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
5
400
0.172
50
400
0.310
150
400
0.370
Table 7.42 Adjustable Frequency Drive, P4K0, T4
MG20N622
Design Guide
U
dU/dt
PEAK
[kV]
[kV/μsec]
0.608
1.993
0.580
0.832
0.574
0.661
U
dU/dt
PEAK
[kV]
[kV/μsec]
0.626
2.581
0.574
1.929
0.538
0.977
U
dU/dt
PEAK
[kV]
[kV/μsec]
0.598
1.593
0.566
0.843
0.546
0.559
U
dU/dt
PEAK
[kV]
[kV/μsec]
0.598
1.593
0.566
0.843
0.546
0.559
dU/dt
U
PEAK
[kV]
[kV/μsec]
0.690
0.862
0.985
0.985
1.045
0.947
dU/dt
U
PEAK
[kV]
[kV/μsec]
0.890
4.156
2.564
1.190
1.770
Danfoss A/S © 09/2014 All rights reserved.
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
5
400
0.04755
50
400
0.207
150
400
0.6742
Table 7.43 Adjustable Frequency Drive, P7K5, T4
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
15
400
0.408
100
400
0.364
150
400
0.400
Table 7.44 Adjustable Frequency Drive, P11K, T4
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
36
400
0.422
100
400
0.464
150
400
0.896
Table 7.45 Adjustable Frequency Drive, P15K, T4
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
36
400
0.344
100
400
1.000
150
400
1.400
Table 7.46 Adjustable Frequency Drive, P18K, T4
AC line
Rise time
Cable
voltage
length [m]
[V]
[μsec]
36
400
0.232
100
400
0.410
150
400
0.430
Table 7.47 Adjustable Frequency Drive, P22K, T4
AC line
Cable
voltage
Rise time
[μsec]
length [m]
[V]
15
400
0.271
100
400
0.440
150
400
0.520
Table 7.48 Adjustable Frequency Drive, P30K, T4
U
dU/dt
PEAK
[kV]
[kV/μsec]
0.739
8.035
1.040
4.548
1.030
2.828
U
dU/dt
PEAK
[kV]
[kV/μsec]
0.718
1.402
1.050
2.376
0.980
2.000
U
dU/dt
PEAK
[kV]
[kV/μsec]
1.060
2.014
0.900
1.616
1.000
0.915
U
dU/dt
PEAK
[kV]
[kV/μsec]
1.040
2.442
1.190
0.950
1.040
0.596
U
dU/dt
PEAK
[kV]
[kV/μsec]
0.950
3.534
0.980
1.927
0.970
1.860
U
dU/dt
PEAK
[kV/μsec]
[kV]
1.000
3.100
1.000
1.818
0.990
1.510
183
7
7