Danfoss VLT AQUA Drive FC 202 Design Manual page 157

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
Type designation
1)
High/normal overload
Typical shaft output [kW]
Typical shaft output at 460 V [hp]
6)
Protection rating IP20/Chassis
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
Output current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x441–480 V) [A]
Intermittent (3x441–480 V) [A]
Continuous kVA at 400 V [kVA]
Continuous kVA at 460 V [kVA]
Maximum input current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous(3x441–480 V) [A]
Intermittent (3x441–480 V) [A]
Maximum pre-fuses [A]
Additional specifications
Protection ratings IP20, IP21
2)
maximum cable cross-section
for
line power, motor, brake, and load
2
sharing [mm
] ([AWG])
Protection ratings IP55, IP66
maximum cable cross-section
2)
for
line power, motor, brake, and load
2
sharing [mm
] ([AWG])
2)
Maximum cable cross-section
for
disconnect [mm
2
] ([AWG])
Estimated power loss
3)
4)
at rated maximum load [W]
5)
Efficiency
Table 7.8 Line Power Supply 3x380–480 V AC, P2K2–P7K5
MG20N622
Design Guide
P2K2
P3K0
HO
NO
HO
NO
2.2
3.0
2.9
4.0
A2
A2
A4/A5
A4/A5
5.6
7.2
8.4
6.2
10.8
7.9
4.8
6.3
7.2
5.3
9.5
6.9
3.9
5.0
3.8
5.0
5.0
6.5
7.5
5.5
9.8
7.2
4.3
5.7
6.5
4.7
8.6
6.3
20
20
88
116
0.97
0.97
Danfoss A/S © 09/2014 All rights reserved.
P4K0
P5K5
HO
NO
HO
4.0
5.5
5.3
7.5
A2
A3
A4/A5
A5
10
13
15.0
11.0
19.5
8.2
11
12.3
9.0
16.5
6.9
9.0
6.5
8.8
9.0
11.7
13.5
9.9
17.6
7.4
9.9
11.1
8.1
14.9
20
30
4, 4, 4 (12, 12, 12)
(minimum 0.2 (24))
4, 4, 4 (12, 12, 12)
6, 4, 4 (10, 12, 12)
124
187
0.97
0.97
P7K5
NO
HO
NO
7.5
10
A3
A5
16
14.3
24.0
17.6
14.5
12.1
21.8
16.0
11.0
11.6
14.4
12.9
21.6
15.8
13.0
10.9
19.5
14.3
30
225
0.97
155
7
7