Specifications
8.1.3 Line Power Supply 3x525–600 V AC
Type Designation
Typical Shaft Output [kW]
IP20/Chassis
IP21/NEMA 1
IP55/Type 12
IP66/NEMA 4X
Output current
Continuous (3 x 525–550 V) [A]
Intermittent (3 x 525–550 V) [A]
Continuous (3x525–600 V) [A]
Intermittent (3x525–600 V) [A]
Continuous kVA (525 V AC) [kVA]
Continuous kVA (575 V AC) [kVA]
Max. input current
Continuous (3x525–600 V) [A]
Intermittent (3x525–600 V) [A]
Additional specifications
Estimated power loss
4)
at rated max. load [W]
5)
IP20 max. cable cross-section
(line
power, motor, brake and load
2
sharing) [mm
/(AWG)]
IP55, IP 66 max. cable cross-section
(line power, motor, brake and load
2
sharing) [mm
/(AWG)]
Max. cable cross-section with
disconnect
Line power disconnect switch
included:
Efficiency
3)
Table 8.6 Line Power Supply 3x525–600 V AC - Normal overload 110% for 1 minute, P1K1-P7K5
®
VLT
HVAC Drive Instruction Manual
P1K1
P1K5
P2K2
1.1
1.5
2.2
A3
A3
A3
A3
A3
A3
A5
A5
A5
A5
A5
A5
2.6
2.9
4.1
2.9
3.2
4.5
2.4
2.7
3.9
2.6
3.0
4.3
2.5
2.8
3.9
2.4
2.7
3.9
2.4
2.7
4.1
2.7
3.0
4.5
50
65
92
5)
0.97
0.97
0.97
MG11AJ22 - Rev. 2013-09-13
P3K0
P3K7
P4K0
3.0
3.7
4.0
A3
A2
A3
A3
A2
A3
A5
A5
A5
A5
A5
A5
5.2
-
6.4
5.7
-
7.0
4.9
-
6.1
5.4
-
6.7
5.0
-
6.1
4.9
-
6.1
5.2
-
5.8
5.7
-
6.4
122
-
145
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
6, 4, 4 (12, 12, 12)
4/12
0.97
-
0.97
P5K5
P7K5
5.5
7.5
A3
A3
A3
A3
A5
A5
A5
A5
9.5
11.5
10.5
12.7
9.0
11.0
9.9
12.1
9.0
11.0
9.0
11.0
8.6
10.4
9.5
11.5
8
195
261
0.97
0.97
57
8