Line Power Supply 1X380-480 V Ac - Danfoss VLT AQUA Drive FC 202 Design Manual

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
7.1.3 Line Power Supply 1x380–480 V AC
Type designation
Typical shaft output [kW]
Typical shaft output at 240 V [hp]
Protection rating IP21/Type 1
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
Output current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x441–480 V) [A]
Intermittent (3x441–480 V) [A]
Continuous kVA at 400 V [kVA]
Continuous kVA at 460 V [kVA]
Maximum input current
Continuous (1x380–440 V) [A]
Intermittent (1x380–440 V) [A]
Continuous (1x441–480 V) [A]
Intermittent (1x441–480 V) [A]
Maximum pre-fuses [A]
Additional specifications
Maximum cable cross-section for line power, motor, and brake
[mm
2
]] ([AWG])
3)
Estimated power loss
at rated maximum load [W]
5)
Efficiency
Table 7.6 Line Power Supply 1x380–480 V AC, Normal Overload 110% for 1 Minute, P7K5–P37K
MG20N622
Design Guide
P7K5
7.5
10
B1
B1
B1
16
17.6
14.5
15.4
11.0
11.6
33
36
30
33
63
10 (7)
4
300
0.96
Danfoss A/S © 09/2014 All rights reserved.
P11K
P18K
11
18.5
15
25
B2
C1
B2
C1
B2
C1
24
37.5
26.4
41.2
21
34
23.1
37.4
16.6
26
16.7
27.1
48
78
53
85.5
41
72
46
79.2
80
160
35 (2)
50 (1/0)
440
740
0.96
0.96
P37K
37
50
C2
C2
C2
73
80.3
65
71.5
50.6
51.8
7
7
151
166
135
148
250
120 (4/0)
1480
0.96
153

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents