Danfoss VLT AQUA Drive FC 202 Design Manual page 176

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Specifications
525–690 V, Enclosure Sizes A, B, and C
Enclosure
A3
B2
7
7
C2
C3
Table 7.22 525–690 V, Enclosure Sizes A, B, and C
174
®
VLT
Power [kW (hp)]
Recommended fuse size
1.1 (1.5)
gG-6
1.5 (2)
gG-6
2.2 (3)
gG-6
3 (4)
gG-10
4 (5)
gG-10
5.5 (7.5)
gG-16
7.5 (10)
gG-16
11 (15)
gG-25
15 (20)
gG-25
18 (24)
gG-32
22 (30)
gG-32
30 (40)
gG-40
37 (50)
gG-63
45 (60)
gG-63
55 (75)
gG-80
75 (100)
gG-100
37 (50)
gG-100
45 (60)
gG-125
Danfoss A/S © 09/2014 All rights reserved.
AQUA Drive FC 202
Recommended
maximum fuse
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-63
gG-63
gG-80
gG-100
gG-125
gG-160
gG-125
gG-160
Recommended circuit
Maximum trip
breaker
level [A]
Danfoss
CTI25M 10-16
16
CTI25M 10-16
16
CTI25M 10-16
16
CTI25M 10-16
16
CTI25M 10-16
16
CTI25M 10-16
16
CTI25M 10-16
16
MG20N622

Hide quick links: