YASKAWA PROFIBUS-DP SI-P3 Technical Manual page 45

Ac drive option
Hide thumbs Also See for PROFIBUS-DP SI-P3:
Table of Contents

Advertisement

Example: Reading to d1-17
Command setting
Data type
PKE
IND
PWE
STW
HSW
Response
Data type
PKE
IND
PWE
STW
HSW
Example: Writing to RAM with the Enter command
Command setting
Data type
PKE
IND
PWE
STW
HSW
Note: When F6-32 = 3 or 5, parameters are validated by writing these parameters to the drive and automatically executing the Enter
command at the same time.
Response
Data type
PKE
IND
PWE
STW
HSW
YASKAWA ELECTRIC SIEP C730600 82D YASKAWA AC Drive Option SI-P3 Technical Manual
8 Parameter Process Data Object Formats
Settings
6029H
6: Request parameter value from array
29H = 41 (d1 parameter)
11H
11H = 17 (d1-17)
0
N/A
up to Master command
up to Master command
Settings
4029H
4: Transfer parameter value (array word)
29H = 41 (d1 parameter)
11H
d1-17
258H
d1-17 value
up to drive status
up to drive status
Settings
212CH
2: Change parameter value (word)
12CH = 300
0
N/A
0
N/A
up to Master command
up to Master command
Settings
112CH
1: Transfer parameter value (word)
12CH = 300
0
N/A
0
N/A
up to drive status
up to drive status
Description
Description
Description
Description
45