Parameter Process Data Object Formats

Supported Parameter Process Data Object (PPO) Type Formats
Set drive parameter F6-32 to 0 to use PPO type formats. The PPO is defined for cyclic data transfer, allowing the master
and the slave to exchange process data (PZD) and parameters. Refer to the PROFIBUS specification for more
information on PPO types 1~5.
The option supports five possible PPO type formats:
• PPO type 1 (8 octets PKW + 4 octets PZD)
• PPO type 2 (8 octets PKW + 12 octets PZD)
• PPO type 3 (4 octets PZD)
• PPO type 4 (12 octets PZD)
• PPO type 5 (8 octets PKW + 20 octets PZD)
All PPO Types have the registers STW, ZSW, HSW, and HIW. These registers are not mapped directly to drive registers.
Configuration of Registers
PKE
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
YASKAWA ELECTRIC SIEP C730600 82D YASKAWA AC Drive Option SI-P3 Technical Manual
PKW
PZD1
STW
PKE
IND
PWE
ZSW
PPO TYPE 1: Octet-String 12
PPO TYPE 2: Octet-String 20
PPO TYPE 3: Octet-String 4
PPO TYPE 4: Octet-String 12
PPO TYPE 5: Octet-String 28
PKW: Parameter ID/value
PZD: Process Data, cyclically transferred
PKE: Parameter ID (1st and 2nd octet)
IND: Sub-index (3rd octet), 4th octet is reserved
PWE: Parameter value (5th until 8th octet)
STW: Control word
HSW: Main setpoint
ZSW: Status word
HIW: Main actual value
PPO Write
PNU number
(Refer to Supported PNU on page 40
SPM always 0
See Task ID
8 Parameter Process Data Object Formats
PZD
PZD2
HSW
PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10
HIW
for details)
SPM always 0
See Response ID
When Response ID is 7, see PWE error code
PPO Read