Related Parameters - YASKAWA PROFIBUS-DP SI-P3 Technical Manual

Ac drive option
Hide thumbs Also See for PROFIBUS-DP SI-P3:
Table of Contents

Advertisement

6 Related Parameters

6
Related Parameters
The parameters in
Table 9
before starting network communications. Refer to the manual packaged with the drive for details on setting parameters.
Note: Hex.: MEMOBUS addresses that you can use to change parameters over network communication are represented in hexadecimal
numbers.
No.
Name
(Hex.)
b1-01
(0180)
Reference 1 Source
<1>
b1-02
(0181)
Run Command 1 Source
<1>
F6-01
Communication Error
(03A2)
Selection
F6-02
Comm External Fault (EF0)
(03A3)
Detect
F6-03
Comm External Fault (EF0)
(03A4)
Select
F6-06
Torque Reference/Limit by
(03A7)
Comm
<5>
F6-07
MultiStep Ref Priority
(03A8)
Select
F6-08
Comm Parameter Reset
(036A)
@Initialize
F6-14
Communication Error Auto
(03BB)
Reset
<8> <9>
F6-30
PROFIBUS-DP Node
(03CB)
Address
<10> <11>
F6-31
PROFIBUS-DP Clear
(03CC)
Mode Selection
24
set the drive for operation with the option. Confirm proper setting of all parameters in
Table 9 Related Parameters
Selects the input method for frequency reference.
0: Keypad
1: Analog Input
2: Memobus/Modbus Communications
3: Option PCB
4: Pulse Train Input
Selects the input method for the Run command.
0: Keypad
1: Digital Input
2: Memobus/Modbus Communications
3: Option PCB
Selects drive response when a bUS error is detected during communications with the
option.
0: Ramp to Stop
1: Coast to Stop
2: Fast Stop (Use C1-09)
3: Alarm Only
<2>
4: Alarm - Run at d1-04
5: Alarm - Ramp to Stop
Selects the condition for external fault detection (EF0).
0: Always detected
1: Detection during run only
Selects drive response for external fault input (EF0) detection during option
communications.
0: Ramp to Stop
1: Coast to Stop
2: Fast Stop (Use C1-09)
3: Alarm Only
<2>
Selects whether to enable or disable the torque reference and torque limit received
from the communication option card.
0: Disabled
1: Enabled
<6>
0: MultiStep References Disabled
1: MultiStep References Enabled
Selects whether communication-related parameters F6- and F7- are set back
to original default values when the drive is initialized using parameter A1-03.
0: No Reset - Parameters retained
1: Reset - Back to factory default
Note: The setting value is not changed even when F6-08 is set to 1 and the drive is
initialized using A1-03.
Enables or disables the Communication Error Auto Reset.
0: Disabled
1: Enabled
Sets the node address.
Selects the action to take after a "Clear Mode" command is received.
0: Resets to 0
1: Maintains the previous value
YASKAWA ELECTRIC SIEP C730600 82D YASKAWA AC Drive Option SI-P3 Technical Manual
Description
<2> <3>
<3>
Table 9
Values
Default: 1
Range: 0 to 4
(Set to 3 for
SI-P3)
Default: 1
Range: 0 to 3
(Set to 3 for
SI-P3)
Default: 1
Range: 0 to 5
<4>
Default: 0
Range: 0, 1
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 0
<7>
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Min: 0
Max: 125
Default: 0
Range: 0, 1