6 Related Parameters
No.
Name
(Hex.)
F7-77
(0791)
PZD8 Read
<8> <9>
F7-78
(0792)
PZD9 Read
<8> <9>
F7-79
(0793)
PZD10 Read
<8> <9>
<1> Set b1-02 = 3 to start and stop the drive with the PROFIBUS-DP master device using serial communications.
Set b1-01 = 3 to control the frequency reference of the drive via the master device.
<2> Setting this parameter to 3 or 4 will cause the drive to continue operation after detecting a fault. Take proper measures such as installing an
emergency stop switch when using settings 3 or 4.
<3> Refer to the drive manual to know if settings 4 and 5 are available. Settings 4 and 5 are available in A1000 software versions PRG: 1021 and
later.
<4> The setting range for 1000-Series drives is different for different software versions. Refer to the instruction manual of a specific drive for more
information.
<5> Control method availability of this parameter depends on product series.
 1000-Series Drives: Parameter is available in CLV, AOLV/PM, and CLV/PM.
In AOLV/PM, this value is read as the Torque Limit.
 GA500 Drive: Parameter is available in OLV, AOLV/PM, and EZOLV.
This value is read as the Torque Limit.
 GA700, GA800 Drives: Parameter is available in OLV, CLV, AOLV, AOLV/PM, CLV/PM, and EZOLV.
In OLV and EZOLV, this value is read as the Torque Limit.
<6> The setting specifies that network communications provide the torque reference or torque limit. The motor may not rotate if the PLC does not
supply a torque reference or torque limit.
<7> Default setting is 1 for GA500.
<8> Available in A1000 software versions PRG: 1021 and later.
<9> Available in option software versions PRG: 2103 and later. Refer to the option package labeling in the field designated "PRG" (four digit
number)" or the option labeling in the field designated "C/N" (S + four digit number)" to identify the option software version.
<10> All node addresses must be unique. Node addresses 0, 1, and 2 are typically reserved for control, maintenance, and diagnostic equipment. The
"Err" LED will illuminate when a value of 0 or a value greater than 125 is entered.
<11> Cycle power for setting changes to take effect.
<12> Requires also setting bit 0 and 4 to issue Run command.
<13> Available in option software versions PRG: 2104 and later. Refer to the option package labeling in the field designated "PRG" (four digit
number)" or the option labeling in the field designated "C/N" (S + four digit number)" to identify the option software version.
<14> When writing this parameter to the drive through the PROFIBUS-DP network, the parameter is validated by automatically executing the Enter
command.
26
Sets MEMOBUS/Modbus address for PZD8 Read (PPO Read).
The value of 0 to 2 disables the PZD8 Read.
Sets MEMOBUS/Modbus address for PZD9 Read (PPO Read).
The value of 0 to 2 disables the PZD9 Read.
Sets MEMOBUS/Modbus address for PZD10 Read (PPO Read).
The value of 0 to 2 disables the PZD10 Read.
Refer to STW/ZSW on page 36
YASKAWA ELECTRIC SIEP C730600 82D YASKAWA AC Drive Option SI-P3 Technical Manual
Description
for more information.
Values
Default: 0H
Min: 0H
Max: FFFFH
Default: 0H
Min: 0H
Max: FFFFH
Default: 0H
Min: 0H
Max: FFFFH