YASKAWA PROFIBUS-DP SI-P3 Technical Manual page 12

Ac drive option
Hide thumbs Also See for PROFIBUS-DP SI-P3:
Table of Contents

Advertisement

4 Option Components
LED
RUN ERR COMM BF
: On /
: Flashing /
12
Table 5 LED Operation After Power-up Diagnostic
Communication
Status
Drive has no power.
No power
Option is not properly connected to the
drive or is not receiving enough power.
• Checking
• Option is reading the node address or
connection with
parameter configuration.
the drive
• Waiting for initial input data from
• Waiting for data
master device.
from the master
Option
self-diagnostics
The option is damaged.
error
• Problem initializing the drive and the
Problem connecting
option.
to the drive
• Incorrect node address.
Waiting for data
Waiting for data from the master device.
from the master
(Set_Parm_Message or
device
Chk_Cfg_Message)
Incorrect data or
The communication settings in the
option time out
master are set incorrectly.
waiting for data
Sending or
receiving data
: Off
YASKAWA ELECTRIC SIEP C730600 82D YASKAWA AC Drive Option SI-P3 Technical Manual
Possible Cause
Solution
Check all wiring to the drive, then turn on the power.
Shut off the drive and make sure the option is
connected properly. Turn the power back on.
Cycle power to the drive. If the LED status does not
change, replace the option.
• Cycle power to the drive. If the LED status does
not change, replace the option.
• Check the node address setting in the drive (F6-30)
• Check master network settings.
• Make sure the master device is operating normally.
• Check terminal resistance settings on the data line.
• Check for problems with the data line and
connector.
• Check if the data line is connected properly to
communication connector CN5.
Check the communication settings in the master.