Product Overview; Elx1052 - Introduction; Fig. 4 Elx1052 - 2-Channel Digital Input Terminal For Namur Sensors, Ex I - Beckhoff ELX1052 Operating Manual

Two, four and eight channel digital input terminals for namur sensors, ex i
Hide thumbs Also See for ELX1052:
Table of Contents

Advertisement

Product overview

2
Product overview
2.1

ELX1052 - Introduction

Fig. 4: ELX1052 - 2-channel digital input terminal for NAMUR sensors, Ex i
The ELX1052 digital input terminal acquires signals from NAMUR field devices according to EN 60947-5-6.
The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way, a wire
breakage or short-circuit can be detected in addition to the switching state. The LEDs indicate signal or any
error states, channel by channel. The sensor supply is equipped with voltage and current limitation for each
channel.
12
Version: 2.0.0
ELX1052, ELX1054 and ELX1058

Advertisement

Table of Contents
loading

This manual is also suitable for:

Elx1054Elx1058

Table of Contents